DEH41181 Rev01 g SMR2 Modbus User Manual
SMR2 Modbus User Manual 7 Test mode -- RW 5 150/160 6 250/250 7 400/400 8 600/630 9 800/800 10 1200/1250 11 1600/1600 12 350 13 500 0007 Infor
SMR2 Modbus User Manual 8 LT Accumulators (A, B, C & N) give normalized values and are typically max 1.25. Hence, they are multiplied with 10,000
SMR2 Modbus User Manual Interpretation of SOS values The Sum Of Squares values (SOS) of a phase is a measure of the RMS value of current flowing thr
SMR2 Modbus User Manual 10Normal mode - RO 3002 Seconds 0 - 59 Test mode RW Unsigned int (Unused) 3003 Long Time Pickup 0-15 Normal Mode--RO ___
SMR2 Modbus User Manual 119 GFA Reset (In GFA module only) 3008 Ground Fault delay 0-9 Normal Mode RO _________ Test Mode RW Value second
SMR2 Modbus User Manual 12 Test mode RW Normal mode – RO 3019 Rating Plug Date Code high 0-9999 Test mode RW Normal mode - RO 3020 Rating P
SMR2 Modbus User Manual 13 3029 Flag Cleared Byte 00 & 0xFF Normal mode - RO 00 Cleared (trip history can not be shown on Flag Module LEDs)
SMR2 Modbus User Manual Reg Contents Units/ Range Type R/W Format 2000 Event Code – Event 1 0-256 RO Unsigned int 2001 Hour 0 R
SMR2 Modbus User Manual 15 Interpretation of Event Codes The following table describes the meaning of each event code Event Code (Hex) Mea
SMR2 Modbus User Manual 16 Bit position in Bit map Bit Position in Bitmap Meaning Event code (Hex) 0 0 No Remote Trip 1 Remote Trip 6 1
SMR2 Modbus User Manual g GE Consumer & Industrial General Electric Company 41 Woodford Ave., Plainvill
SMR2 Modbus User Manual i Table of Contents Introduction ...
SMR2 Modbus User Manual 2 Introduction The SMR2 trip unit has an optional communications module that facilitates monitoring of the trip unit via a ma
SMR2 Modbus User Manual MODBUS ADDRESSES The master device addresses a specific slave device by placing the 8-bit slave address in the address fie
SMR2 Modbus User Manual Figure2. Connection between Breaker and FAMECM module 3 Communication Environment • The trip unit is always the sla
SMR2 Modbus User Manual 464h 03h 0Bh C2h 00h 03h CRCl CRCh Response: (register contents: 3010 = 022Bh, 3010 = 0000h, 3012 = 0066h) Data (n bytes)
SMR2 Modbus User Manual 5Address (1 byte) Code (1 byte) Previous transmitted data (2 bytes) 64h 38h xxh xxh xxh xxh xxh xxh xxh xxh xxh CRCl CRCh
SMR2 Modbus User Manual 2 Register Map While modbus communication with Target Communication Accessory module, all the registers are read only re